Discover the Hose Stream 180 First Responder Steel-Tex Fire Shutter (SFS). This opening protective meets the requirement for a 3-hour fire protection rating, making it ideal for use in a 3- or 2-hour fire-rated wall or fire barrier assembly. Different from our standard Hose Stream 180 , this product features a First Responder Door for Ingress and Egress per NFPA 101.

Please see the below IBC Table regarding Opening Fire Protection Assemblies (Table 175.3).

2-Hour to 3-Hour Fire Resistant Curtains with Ingress & Egress

The Hose Stream 120 First Responder is used to protect openings for up to a 2-hour fire wall or fire barrier per IBC 715.3. Its defining feature is a First Responder Door for Ingress and Egress, which needs no fastener, magnet, or latch at the door opening. The weight of the fabric keeps the door closed, and it takes less than five pounds of force to open. There is a side hinge at the bottom bar that allows for the fabric to swing when force is applied.

The Hose Stream 120 First Responder is a deployable Steel-Tex fire shutter system with a standard fail-safe battery backup and options for leading-edge safety sensors. This shutter is composed of a wired reinforced Steel-Tex on a round steel tube in a fire-rated assembly. The Steel-Tex fire shutter remains retracted above the finished ceiling until activated by a fire alarm or smoke alarm. Once activated, the shutter descends at 6 inches per second, creating a smoke and fire barrier. The fire shutter can also be non-motorized when activated by a fusible link for smaller openings.

To learn more about this system, reach out to U.S. Smoke & Fire today.

Hose Stream Series - UL 10B Products
Finishing Touches

Our Design Options

Call us to learn about our custom design options.

Ceiling Finishes

Flushed

Recessed

Soffit

Wall Finishes

Example

Example

Example

Streamlined & Comprehensive

Learn About the Features of This Durable Fire Protection System

Protection Rating

The U.S. Smoke & Fire Hose Stream 180 First Responder shutter is tested to UL 10B standards. It has a minimum of 3 hour fire protection rating to be sufficient for an opening protective in a 3-hour fire barrier enclosing wall per IBC Table. A hose stream test (ASTM E2226) is conducted as part of the fire endurance testing and the shutter shall have passed this test.

Head-Box and Release

The head-box is mounted using threaded rods and unistruts. For power, 120V to the motor side of the head-box. The Steel-Tex Fire Shutter (SFS) will release when receiving a signal from a fire alarm system (FAS). Push-to-exit buttons are installed for egress. Leading edge safety sensor option. BMS relay option. Beam Sensor option.

Assembly

The Hose Stream 120 First Responder is a multibarrel assembly with Steel-Tex fabric overlap of 24″. A building occupant can step through the overlap to the opposing side of the shutter. The inverted T bottom bar holds the overlap in place for the length of the headbox.

Hose Stream 180 First Responder Testing & Rating

Our innovative steel fiber fabric shutters were created to withstand the Hose Stream Test—a structural integrity test that defines safety measures in building materials. The Hose Stream 180 First Responder is tested in accordance to UL 10B and ASTM E2226 (Hose Stream Test) standards for 180 minutes.

When testing to meet these standards, we heat a product specimen in a testing furnace for the designated period of time (in this case, 180 minutes) and subject it to a 35 PSI hose stream or greater. This higher level of testing holds these textile shutters to elevated standards of safety and quality.

The Hose Stream 180 First Responder curtain is certified by Guardian for NFPA 252 Compliance and by Intertek as a UL864 Releasing Device USA & Canada 110V or 220V.

Stay Connected With Us

Start Planning Your Project

U.S. Smoke & Fire’s experienced team understands the importance of achieving a delicate balance between quality and cost to deliver optimal solutions that precisely meet client standards. We specialize in tailor-made smoke and fire barrier designs for a wide range of spaces. Expansive atriums, narrow corridors, elevators, lobbies, and offices are just a few examples of the areas we’ve helped protect. Our fire protection strategies comply with building codes while offering unparalleled design flexibility and aesthetic appeal.

Make your custom project stand out with U.S. Smoke & Fire. We offer gravity fail-safe, fire-rated curtain walls meticulously crafted from specialized steel textile materials. These curtains are designed to provide maximum protection against smoke and fire, seamlessly integrating with your space’s unique vision. With an unwavering commitment to enduring quality and lasting protection, our fire-rated curtain walls guarantee peace of mind for you and your occupants.

Connect with our team today to realize your project plans, receive prompt responses to any inquiries, and witness firsthand the expertise and dedication that sets us apart.

Name(Required)

Back To Top