The Hose Stream 120 First Responder Steel-Tex Fire Shutter (SFS) is an opening protective that meets the requirement for a 90-minute fire protection rating. With this rating, it can be used in a 2-hour fire-rated wall or fire barrier assembly. This product differs from our standard Hose Stream 120 in that it features a First Responder Door for Ingress and Egress per NFPA 101.
Please see the below IBC Table regarding Opening Fire Protection Assemblies (Table 175.3).
2-Hour Fire Resistant Curtains with Ingress & Egress
The Hose Stream 120 First Responder is used to protect openings for up to a 2-hour fire wall or fire barrier per IBC 715.3. Its defining feature is a First Responder Door for Ingress and Egress, which needs no fastener, magnet, or latch at the door opening. The weight of the fabric keeps the door closed, and it takes less than five pounds of force to open. There is a side hinge at the bottom bar that allows for the fabric to swing when force is applied.
The Hose Stream 120 First Responder is a deployable Steel-Tex fire shutter system with a standard fail-safe battery backup and options for leading-edge safety sensors. This shutter is composed of a wired reinforced Steel-Tex on a round steel tube in a fire-rated assembly. The Steel-Tex fire shutter remains retracted above the finished ceiling until activated by a fire alarm or smoke alarm. Once activated, the shutter descends at 6 inches per second, creating a smoke and fire barrier. The fire shutter can also be non-motorized when activated by a fusible link for smaller openings.
To learn more about this system, reach out to U.S. Smoke & Fire today.
Our Design Options
Call us to learn about our custom design options.
Ceiling Finishes
Wall Finishes
Learn About the Features of This Durable Fire Protection System

Hose Stream 120 First Responder Testing & Rating
These innovative steel fiber fabric shutters were created to withstand the Hose Stream Test—a structural integrity test that defines safety measure in building materials. The Hose Stream 120 First Responder is tested in accordance with UL 10B and ASTM E2226 (Hose Stream Test) standards for 90 minutes.
For testing against these standards, we place a product specimen in a testing furnace for a period of time (in this case, 90 minutes) and subject it to a 35 PSI hose stream or greater. This rigorous level of testing holds these fire curtains to a higher level of quality and safety.
This product is certified by Guardian for NFPA 252 Compliance and by Intertek as a UL864 Releasing Device USA & Canada 110V or 220V.
Stay Connected With Us
Start Planning Your Project
Our experienced team at U.S. Smoke & Fire recognizes the significance of striking a balance between quality and cost to deliver optimal solutions that meet or surpass your expectations. We specialize in creating smoke and fire barrier designs tailored precisely to your space, whether it be expansive atriums, narrow corridors, elevators, or versatile, size-adjustable meeting rooms. Rest assured that our fire protection strategies align with building codes while maintaining strong design flexibility and aesthetic appeal.
At U.S. Smoke & Fire, we support customized projects with our gravity fail-safe fire-rated curtain walls crafted from specialized steel-textile materials. These curtains are meticulously designed for protective applications against smoke and fire, tailored to seamlessly integrate with the unique vision you have for your space. With a commitment to enduring quality, our fire-rated curtain walls provide lasting protection and peace of mind for you and your building’s occupants.